DocumentCode :
2847480
Title :
A Practical Approach to Eliminating DC Magnetic Flux from the Series Transformer of a Dynamic Voltage Restorer
Author :
Jimichi, Takushi ; Fujita, Hideaki ; Akagi, Hirotumi
Author_Institution :
Tokyo Inst. of Technol., Tokyo
fYear :
2007
fDate :
2-5 April 2007
Firstpage :
1673
Lastpage :
1679
Abstract :
This paper proposes a control method for eliminating dc magnetic flux from the series transformer of a DVR. The method is characterized by intentionally injecting no compensating voltage during a one-sixth line cycle (=3.3 ms at 50 Hz). The control sequence is independent of an initial phase angle of a voltage sag, thus requiring no flux detection. The period, during which no compensating voltage is injected, is one-third as short as that of an existing method. This paper verifies the effectiveness and viability of the proposed method, using a 200-V, 5-kW laboratory system. The proposed method brings no dc magnetic flux to the series transformer.
Keywords :
power supply quality; power transformers; voltage control; DC magnetic flux; control method; control sequence; dynamic voltage restorer; series transformer; voltage sag; Capacitors; Circuit faults; Costs; Magnetic flux; Phase detection; Power quality; Power system dynamics; Power system restoration; Voltage control; Voltage fluctuations;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Conversion Conference - Nagoya, 2007. PCC '07
Conference_Location :
Nagoya
Print_ISBN :
1-4244-0844-X
Electronic_ISBN :
1-4244-0844-X
Type :
conf
DOI :
10.1109/PCCON.2007.373187
Filename :
4239377
Link To Document :
بازگشت