DocumentCode :
2847568
Title :
The analysis of an ungrounded wye-delta transformer bank serving an induction motor and single-phase lighting loads
Author :
Kersting, W.H. ; Rathbun, J.S.
Author_Institution :
New Mexico State Univ., Las Cruces, NM, USA
fYear :
1999
fDate :
1999
Abstract :
This paper documents the detailed analysis of the three-phase ungrounded wye-delta transformer bank serving a combination three-phase induction motor and single-phase lighting load. A 3×3 transfer function matrix is developed that makes if possible to determine the load line-to-line voltages with a knowledge of the primary voltages of the transformer bank. Included in the transfer function matrix are the transformer impedances, unsymmetrical secondary impedance matrix and the impedances of the motor and single-phase lighting load
Keywords :
impedance matrix; induction motors; lighting; power transformers; transfer function matrices; 3×3 transfer function matrix; distribution transformer connection models; lighting load impedance; load line-to-line voltages; motor impedance; single-phase lighting load; three-phase induction motor load; transformer impedances; ungrounded wye-delta transformer bank; unsymmetrical secondary impedance matrix; Aggregates; Electric variables; Equations; Impedance; Induction motors; Kirchhoff´s Law; Low voltage; Phase transformers; Text analysis; Transfer functions;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Rural Electric Power Conference, 1999
Conference_Location :
Indianapolis, IN
Print_ISBN :
0-7803-5244-0
Type :
conf
DOI :
10.1109/REPCON.1999.768692
Filename :
768692
Link To Document :
بازگشت