Title :
A new criterion for GCB open-phase protection in large pumped storage units
Author :
Heting Li ; Lin Gui ; Jun Chen ; Rufei He ; Shichao Liu ; Xiaoyu Wang
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Abstract :
In the Guangzhou Pumped Storage Power Station A (GPSPSA), a single-phase disconnection fault of a generator circuit breaker (GCB) caused the preemptive action of a zero sequence overvoltage protection at the low voltage side of the main transformer which expanded the accident scope. To investigate this disconnection fault, a simulation model is built in the PSCAD environment and is verified by the dynamic simulation system of Nari-relays Company. Then the GCB single-phase disconnection fault in GPSPSA is also reproduced. Results of simulations and experimental studies reveal some fault features to help understanding this disconnection fault. Based on these results, a new criterion, using the phase angle difference of the zero sequence fundamental voltage between the generator terminal and the low voltage side of the main transformer is proposed for the GCB open-phase protection.
Keywords :
circuit breakers; overvoltage protection; power generation faults; power generation protection; power transformers; pumped-storage power stations; GCB open-phase protection; GCB single-phase disconnection fault; GPSPSA; Guangzhou pumped storage power station A; PSCAD environment; dynamic simulation system; generator circuit breaker; generator terminal; large pumped storage units; phase angle difference; transformer; zero sequence fundamental voltage; zero sequence overvoltage protection; Circuit faults; Companies; Generators; Load modeling; Low voltage; PSCAD; Voltage control;
Conference_Titel :
Electrical and Computer Engineering (CCECE), 2015 IEEE 28th Canadian Conference on
Conference_Location :
Halifax, NS
Print_ISBN :
978-1-4799-5827-6
DOI :
10.1109/CCECE.2015.7129194