• DocumentCode
    2863499
  • Title

    Specifications and standards scene [HV switchgear]

  • Author

    Crawley, David

  • fYear
    1997
  • fDate
    35534
  • Firstpage
    42675
  • Abstract
    The UK Regional Electricity Companies (REC) requirements for internal arcing tests for high voltage switchgear up to 36 kV are based on IEC298, complemented by EA Technical Specifications (EATS) 41-26 and 41-27. The selection of options from IEC 298, and the specific test arrangements to be used, were introduced in 1991 with the issue of the EATSs. This was against a background of opinion from the electricity industry that internal arcing tests were required and that these would enhance safety in the event of an internal fault. In IEC298 the tests are optional and by agreement
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Risk Reduction: Internal Faults in T&D Switchgear (Digest No.: 1997/295), IEE Colloquium on
  • Conference_Location
    Nottingham
  • Type

    conf

  • DOI
    10.1049/ic:19970983
  • Filename
    640512