Research on Protective Distance between Arrester and Transformer of 220kV AIS Substation
Author :
Zhou, Yuanyuan ; Zhou, Lixing ; Li, Lei ; Gan, Lingxia ; Xu, Yinfeng
Author_Institution :
Coll. of Electr. & Inf. Eng., Changsha Univ. of Sci. & Technol., Changsha, China
Volume :
2
fYear :
2009
fDate :
16-18 Oct. 2009
Firstpage :
236
Lastpage :
239
Abstract :
This article according to internal and external actual situation from the typical 220 kV substation connection, ATP-EMTP simulation program is applied to simulate and analyze under all effect is to be considered, the rules of over-voltage from transformer and the position of arrester is founded, and found that if the incoming line of overhead line to open-substation have CVT, the maximum protective distance is 185 meter else 143 m and other incoming line substation set the arrester in front can satisfy impact insulation level, the reference is provided that the distance between arrester and transformer.
Keywords :
EMTP; arresters; overvoltage protection; power overhead lines; substation protection; AIS substation; ATP-EMTP simulation program; arrester position; overhead line; protective distance; substation connection; transformer overvoltage; voltage 220 kV; Arresters; Capacitance; Educational institutions; Instrument transformers; Lightning; Power cables; Power engineering and energy; Power transformer insulation; Substation protection; Switches; 220kV substation; arrester; lightning incoming surge; over-voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Energy and Environment Technology, 2009. ICEET '09. International Conference on
Conference_Location :
Guilin, Guangxi
Print_ISBN :
978-0-7695-3819-8
Type :
conf
DOI :
10.1109/ICEET.2009.295
Filename :
5366483
Link To Document :
بازگشت