Title :
Automatic reclosing of compact and uprated transmission lines
Author :
BÁn, Gábor ; Bánfai, György ; Prikler, László
Author_Institution :
Tech. Univ. Budapest, Hungary
Abstract :
Environmental compatibility requires reduction of transmission line dimensions. As a consequence. An increase in the number of faults is expected. This can be compensated by improving the success of automatic reclosing. The physics of secondary arcing and the reclosing transient are analysed at uncompensated and shunt-compensated lines. Increasing the dead time is avoidable by means of adaptive single phase reclosing. Reclosing overvoltages, endangering the polluted sections of transmission lines, may be significantly reduced by a coordinated operation of MOAs and controlled switching
Keywords :
arcs (electric); compensation; power overhead lines; switching; adaptive single phase reclosing; adaptive single-phase reclosing; automatic reclosing; compact transmission lines; controlled switching; coordinated operation; environmental compatibility; reclosing overvoltage; secondary arcing; shunt-compensated lines; transmission line dimensions reduction; uncompensated lines; uprated transmission lines; Conductors; Costs; Insulation; Lightning; Poles and towers; Surges; Transient analysis; Transmission lines; Voltage; Wires;