DocumentCode
2871663
Title
Investigation of temperature rise and permissible load current of water-cooled generators with blockage of hollow sub-conductors
Author
Naghashan, M.R. ; Shoar, D. Hekmat
Author_Institution
Power & Water Inst. of Technol., Tehran
fYear
2005
fDate
26-26 Oct. 2005
Firstpage
85
Lastpage
88
Abstract
Temperature rise of insulation can be due to the blockage of the hollow sub-conductors in water-cooled bars. The objective of this project is to make a software simulator to analyze the problem in water-cooled generators in Iran. An experimental setup is constructed to recognize the hollow sub-conductor blockage and its effect on the permissible load current of the generator bar. Results of experiments are used to develop an evaluation software model. The model is applied in air and in hydrogen medium. Measured temperatures of various points on the generator bar show that the hot spot of the insulation can not be detected easily by normal slot RTDs in the machine
Keywords
bars; cooling; electric generators; electric machine analysis computing; hydrogen; machine insulation; temperature measurement; Iran; RTD; air medium; hydrogen medium; insulation temperature rise; software simulator; sub-conductor blockage; temperature measurement; water-cooled generator bar; Bars; Character generation; Conductors; Induction generators; Insulation; Land surface temperature; Power generation; Temperature measurement; Temperature sensors; Water;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation Conference and Electrical Manufacturing Expo, 2005. Proceedings
Conference_Location
Indianapolis, IN
Print_ISBN
0-7803-9145-4
Type
conf
DOI
10.1109/EEIC.2005.1566264
Filename
1566264
Link To Document