A suggested approach for specifying partial discharge testing as a new winding acceptance test
Author :
Stone, Greg
Author_Institution :
Iris Power Eng., Toronto, Ont.
fYear :
2005
fDate :
26-26 Oct. 2005
Firstpage :
159
Lastpage :
162
Abstract :
Partial discharge testing has been used for over 50 years as a diagnostic to assess the insulation condition of motor and generator stator windings rated 3.3 kV and above. As such, most of the North America´s large utility generators already undergo routine on-line PD testing. Many users have expressed a desire to specify allowable PD levels for new stators or rewinds-to ensure acceptable manufacturing and assembly of the winding, especially for global VPI stators. Unfortunately there are no domestic or international standards that describe the acceptable PD levels. If PD tests are to be used as acceptance tests-then the users must insert this in their purchase specifications. One must be very careful when specifying PD for a new machine-to ensure that the test is both meaningful, yet not unreasonably difficult to pass. This paper reviews the reasons for this, and proposes a scientifically defensible way of specifying PD, that is independent of the test equipment used
Keywords :
insulation testing; machine insulation; machine testing; partial discharges; stators; 3.3 kV; North America; insulation condition diagnostics; motor-generator VPI stator winding; partial discharge testing; winding acceptance testing; Bars; Coatings; Coils; IEC standards; Insulation testing; Manufacturing; Partial discharges; Production facilities; Stator windings; Stress;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation Conference and Electrical Manufacturing Expo, 2005. Proceedings
Conference_Location :
Indianapolis, IN
Print_ISBN :
0-7803-9145-4
Type :
conf
DOI :
10.1109/EEIC.2005.1566280
Filename :
1566280
Link To Document :
بازگشت