• DocumentCode
    2872048
  • Title

    Evaluation of medium voltage groundwall insulation exposed to high frequency pulse voltages

  • Author

    Haq, Saeed Ul ; Jayaram, Shesha H. ; Cherney, E.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Waterloo Univ., Ont.
  • fYear
    2005
  • fDate
    26-26 Oct. 2005
  • Firstpage
    194
  • Lastpage
    197
  • Abstract
    Class-F 4.0 kV coils designed for medium voltage induction motors are aged under combined thermal and electrical stresses of 500 h at a constant temperature of 120degC and 200 h at a constant temperature of 150degC and stressed electrically at 60 Hz and with steep-front unipolar pulses of 40 ns rise time. The changes in the partial discharge activity and the dissipation factor as a function of time are reported. During ageing, the temperature profiles are recorded with an infrared camera as a means for determining the highest stressed regions. The experimental results show that pulse ageing is very severe when compared to 60 Hz ageing, despite using a lower pulse voltage, although the location where damage occurs on the groundwall insulation is different
  • Keywords
    ageing; coils; image sensors; induction motor drives; infrared imaging; machine insulation; partial discharges; thermal stresses; variable speed drives; video cameras; 120 C; 150 C; 4 kV; 60 Hz; adjustable speed drive; ageing; armour tape; class-F coil; dissipation factor; electrical stress; groundwall insulation; high frequency pulse; infrared camera; medium voltage induction motor; partial discharge; thermal stress; Aging; Cameras; Coils; Frequency; Induction motors; Insulation; Medium voltage; Partial discharges; Temperature; Thermal stresses;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference and Electrical Manufacturing Expo, 2005. Proceedings
  • Conference_Location
    Indianapolis, IN
  • Print_ISBN
    0-7803-9145-4
  • Type

    conf

  • DOI
    10.1109/EEIC.2005.1566289
  • Filename
    1566289