DocumentCode :
2872048
Title :
Evaluation of medium voltage groundwall insulation exposed to high frequency pulse voltages
Author :
Haq, Saeed Ul ; Jayaram, Shesha H. ; Cherney, E.
Author_Institution :
Dept. of Electr. & Comput. Eng., Waterloo Univ., Ont.
fYear :
2005
fDate :
26-26 Oct. 2005
Firstpage :
194
Lastpage :
197
Abstract :
Class-F 4.0 kV coils designed for medium voltage induction motors are aged under combined thermal and electrical stresses of 500 h at a constant temperature of 120degC and 200 h at a constant temperature of 150degC and stressed electrically at 60 Hz and with steep-front unipolar pulses of 40 ns rise time. The changes in the partial discharge activity and the dissipation factor as a function of time are reported. During ageing, the temperature profiles are recorded with an infrared camera as a means for determining the highest stressed regions. The experimental results show that pulse ageing is very severe when compared to 60 Hz ageing, despite using a lower pulse voltage, although the location where damage occurs on the groundwall insulation is different
Keywords :
ageing; coils; image sensors; induction motor drives; infrared imaging; machine insulation; partial discharges; thermal stresses; variable speed drives; video cameras; 120 C; 150 C; 4 kV; 60 Hz; adjustable speed drive; ageing; armour tape; class-F coil; dissipation factor; electrical stress; groundwall insulation; high frequency pulse; infrared camera; medium voltage induction motor; partial discharge; thermal stress; Aging; Cameras; Coils; Frequency; Induction motors; Insulation; Medium voltage; Partial discharges; Temperature; Thermal stresses;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation Conference and Electrical Manufacturing Expo, 2005. Proceedings
Conference_Location :
Indianapolis, IN
Print_ISBN :
0-7803-9145-4
Type :
conf
DOI :
10.1109/EEIC.2005.1566289
Filename :
1566289
Link To Document :
بازگشت