DocumentCode :
2874578
Title :
Influence of interphase interference to on-line leakage current monitoring of MOA
Author :
Wang, Yongqiang ; Lu, Fangcheng ; Li, Heming
Author_Institution :
Sch. of Electr. Eng., North China Electr. Power Univ., Baoding, China
fYear :
2004
fDate :
18-21 Aug. 2004
Firstpage :
916
Lastpage :
919
Abstract :
MOA is very important in power system. Therefore, on-line monitoring of MOA becomes necessary. Forever because of influence of location and, distributing mode of MOA, the voltage of two other phases affect single MOA by interphase interference, and this will surely influence the monitoring accuracy of MOA´s resistive leakage current. In this paper, we analyze double CT method to eliminate this influence. And we advance the principle of synchronous sampling on multi-lower computer system. Based on these methods, we develop the bus-module on-line leakage current monitoring of MOA. And it has already been successfully used in the project.
Keywords :
computerised monitoring; interference (signal); leakage currents; overvoltage protection; power engineering computing; power system protection; MOA; double CT method; interphase interference; multi-lower computer system; on-line leakage current monitoring; power system; resistive leakage current; synchronous sampling; Aging; Arresters; Computerized monitoring; Interference; Leakage current; Power system protection; Sampling methods; Substation protection; Surge protection; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Microwave and Millimeter Wave Technology, 2004. ICMMT 4th International Conference on, Proceedings
Print_ISBN :
0-7803-8401-6
Type :
conf
DOI :
10.1109/ICMMT.2004.1411680
Filename :
1411680
Link To Document :