• DocumentCode
    2880701
  • Title

    Influence of Power System´s Harmonic Voltage and Interphase Interference to On-line Resistive Leakage Current monitoring of MOA

  • Author

    Yongqiang, Wang ; Fangcheng, Lu ; Jing, Shang ; Heming, Li

  • Author_Institution
    North China Electr. Power Univ., Baoding
  • fYear
    2006
  • fDate
    1-4 Aug. 2006
  • Firstpage
    620
  • Lastpage
    623
  • Abstract
    Surge arrester is an important over voltage protection equipment in substation, and the latent faults of MOA can be found by on-line resistive leakage current monitoring. However, the existence of harmonic voltages in the power system will influence the monitoring accuracy. At the same time, because of influence of location and distributing mode of MOA, the voltage of two other phases affect single MOA by interphase interference, and this will surely influence the monitoring accuracy of MOA´s resistive leakage current too. In this paper, the influence is analyzed and the method to separate the resistive leakage current under the existence of harmonic voltage is analyzed
  • Keywords
    arresters; interference (signal); leakage currents; overvoltage protection; power system harmonics; power system protection; MOA; harmonic voltage; interphase interference; metal oxide surge arrester; on-line resistive leakage current monitoring; over voltage protection equipment; power systems; Arresters; Harmonic analysis; Interference; Leakage current; Monitoring; Power system harmonics; Power system protection; Substation protection; Surge protection; Voltage control; MOA; harmonic voltage; interphase interference; monitoring;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Environmental Electromagnetics, The 2006 4th Asia-Pacific Conference on
  • Conference_Location
    Dalian
  • Print_ISBN
    1-4244-0183-6
  • Type

    conf

  • DOI
    10.1109/CEEM.2006.258031
  • Filename
    4027363