Title
Adaptive settings of distance protection to prevent mal-operation under severe voltage fluctuation
Author
Abidin, Ahmad Farid Bin ; Mohamed, Azah
Author_Institution
Fac. of Electr. Eng., UiTM, Shah Alam, Malaysia
fYear
2011
fDate
27-28 June 2011
Firstpage
162
Lastpage
165
Abstract
A new algorithm for adaptive setting of Zone 3 of distance relays during severe voltage fluctuations is proposed. Conventional relays may mal-operate during under voltage instability condition. The developed algorithm is based on dynamic adjustment of zone 3 setting of distance relays to avoid mal-operation. The proposed algorithm overcomes the pitfall in conventional relays by dynamically changing zone 3 reach setting of the distance relay. The paper describes the new algorithm and presents results obtained from studies on the IEEE 9 bus test system.
Keywords
fault diagnosis; relay protection; IEEE 9 bus test system; adaptive settings; distance protection; distance relays; mal-operation prevention; voltage fluctuations; voltage instability condition; zone 3 reach setting; Presses; Distance Protection; Dynamic Adjustment; Relay Reach Setting; Voltage Instability;