    Thermal zones for more efficient data center energy management

  • Author

    Hamann, Hendrik F. ; López, Vanessa ; Stepanchuk, Andrew

  • Author_Institution
    T.J. Watson Res. Center, IBM, Yorktown Heights, NY, USA
  • fYear
    2010
  • fDate
    2-5 June 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    The optimization of cooling resources within data centers (DCs), which includes the localized provisioning of cooling power with respect to the heat dissipation, can lead to significant reduction of energy consumption. While such matching is rather straightforward for the entire DC, on a more granular level however, the large range of heat densities of today´s IT equipment has made this task much more challenging. One complication comes from the fact there is little operational information, for example, which physical areas (or zones) are supplied by the different air conditioning units (ACUs) so that local cooling demands can be met. Evidently, such zones are not only determined by the placement and air flow produced by each ACU but also by the locations of perforated tiles throughout the DC and many other parameters. Here we present a general methodology for determining such zones. Specifically, we use a simplified physics model to calculate the air flow velocity field within the DC. The novelty of the approach is that the boundary conditions are obtained from real-time measurements. Once the air flow pattern is calculated, we deploy an efficient tracing algorithm, which follows the air from/to each area of the DC back to the originating/returning ACU. The trace connects a specific ACU with its related zone. Each zone can be associated with the actual efficiency of the corresponding ACU by considering the respective utilization of the units (heat removed / nominal heat load removal capacity) or coefficient of performance (COP = heat removed / power consumption for ACU fans). Both COP and ACU utilization can be obtained from real-time temperature and air flow measurements. The paper will also discuss a software tool, which helps operators to use this information for improving DC energy efficiency.
  • Keywords
    air conditioning; cooling; energy consumption; energy management systems; air conditioning units; air flow measurements; coefficient of performance; cooling resources; data center energy management; efficient tracing algorithm; energy consumption reduction; local cooling demands; thermal zones; Air conditioning; Boundary conditions; Cooling; Distributed control; Energy consumption; Energy management; Fluid flow measurement; Physics; Thermal management; Tiles; CFD modeling; Data Center; Energy Efficiency; Energy Management; Potential flow; Thermal Management;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2010 12th IEEE Intersociety Conference on
  • Conference_Location
    Las Vegas, NV
  • ISSN
    1087-9870
  • Print_ISBN
    978-1-4244-5342-9
  • Electronic_ISBN
    1087-9870
  • Type

    conf

  • DOI
    10.1109/ITHERM.2010.5501332
  • Filename
    5501332