DocumentCode :
2890681
Title :
LVRT performance verification of PCS for wind power generation
Author :
Komatsu, Hiroyoshi ; Takahashi, Tatsuro ; Ambo, Tatsuaki
Author_Institution :
Toshiba Mitsubishi-Electr. Ind. Syst. Corp., Fuchu, Japan
fYear :
2013
fDate :
3-6 June 2013
Firstpage :
1176
Lastpage :
1181
Abstract :
A large capacity PCS (Power Conditioning System) applied to PMSG (permanent magnet synchronous generator) of wind turbine has been developed and the operation characteristics of the PCS were tested with the same conditions in actual field operation. The low voltage ride through capability that required in each country grid code was evaluated by a digital simulation and a simulator test with a scale-down model of PCS installing actual control card, a motor generator set and grid simulator. It was confirmed that the PCS continuously operate without disconnection during the low voltage condition simulated by the grid simulator. Then the LVRT capability for actual 2MW-PCS is also evaluated with the digital simulation.
Keywords :
permanent magnet generators; power grids; synchronous generators; wind power plants; wind turbines; LVRT performance verification; PCS; PMSG; actual control card; country grid code; digital simulation; grid simulator; low voltage ride through capability; motor generator set; permanent magnet synchronous generator; power 2 MW; power conditioning system; scale-down model; simulator test; wind power generation; wind turbine; Cooling; Digital simulation; Distributed Bragg reflectors; Inverters; Pulse width modulation; Low Voltage Ride Through; PMSG; large capacity PCS; scale-down model PCS;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
ECCE Asia Downunder (ECCE Asia), 2013 IEEE
Conference_Location :
Melbourne, VIC
Print_ISBN :
978-1-4799-0483-9
Type :
conf
DOI :
10.1109/ECCE-Asia.2013.6579257
Filename :
6579257
Link To Document :