Title
Reliability and Availability Analysis of UPS
Author
Hidaka, Toshimitsu ; Harada, Koosuke
Author_Institution
Kyushu University 36, 6-10-1 Hakozaki Higashi-ku, Fukuoka 812 JAPAN
fYear
1994
fDate
11-15 April 1994
Firstpage
361
Lastpage
366
Abstract
The backup battery of UPS has several kinds of physical failure modes, for example, that is caused by the loss of energy, the stress exposed from outside and the stress from inside. To find an entire failure rate, we consider this effect as a series phenomenon of each failure mode. On the assumption that backup battery of UPS has operation failure p.d.f of Erlang, we investigate the relation between system reliability of UPS and stochastic operation time of battery (for example, mean time or Erlang phase). Also as an example, we compute unavailability. Then we could get the results that its inverter availability has main effect as the important parameter for the availability measure of UPS system.
Keywords
Availability; Battery charge measurement; Inverters; Power supplies; Protection; Reliability; Stochastic systems; Stress; Uninterruptible power systems; Voltage;