Title :
Automotive Type Batteries in Long Term Float and UPS Applications
Author_Institution :
B. C. Hydro and Power Authority, 5 - 1045 Howe Street, Vancouver, B. C. V6Z 2B1
Abstract :
B. C. Hydro has been using lead calcium maintenance-free automotive batteries for over ten years in small 24 VDC communications grade power systems as well as 72 and 120 VDC UPS applications. Over 300 batteries are now in use and experience has been very favourable. Cost savings have been large and as well there have been some safety benefits. Only four failures have been reported: two were traced to cracked separators, one to a poor internal connection, and one to grid corrosion. This paper describes the selection of lead calcium maintenance-free batteries, their charge-discharge curves, the design criteria for various systems, and some maintenance considerations.
Keywords :
Automotive engineering; Batteries; Calcium; Costs; Manufacturing; Particle separators; Power systems; Rectifiers; Safety; Uninterruptible power systems;
Conference_Titel :
Telecommunications Energy Conference, 1986. INTELEC '86. International
Conference_Location :
Toronto, Canada
Print_ISBN :
0-9692316-1-X
DOI :
10.1109/INTLEC.1986.4794451