DocumentCode :
2892986
Title :
Analysis of characteristics of damping compensated by subsynchronous damping control in HVDC system
Author :
Sun, Jibo ; Wang, Xitian ; Xv, Yingxin ; Sun, Huiping
Author_Institution :
Dept. of Electr. Eng., Shanghai Jiao Tong Univ., Shanghai, China
fYear :
2011
fDate :
6-9 July 2011
Firstpage :
428
Lastpage :
432
Abstract :
Subsynchronous Damping Control (SSDC) compensation damping plays a significant role in power system stability in HVDC system. This paper builds a linear model to analysis SSDC compensation damping characteristics based on an EPRI proposed double-ended DC test system. Calculation results show that electrical damping is obviously relevant to some factors, such as generator capacity, DC system transmission capacity and DC/AC system connection strength. The ratios of the electrical damping to the Unit Interaction Factor (UIF) and other two specific constants, which are part of UIF, don´t change significantly. The two constants can be used to indicate characteristics of the electrical damping and represent the `shaft to converter station´ electrical damping transfer characteristic. In this paper, the two constants are called Backward Unit Interaction Factor and Forward Unit Interaction Factor. Therefore, electrical damping characteristics can be represented by UIF and the newly proposed two constants.
Keywords :
DC-AC power convertors; HVDC power convertors; HVDC power transmission; damping; power system stability; power transmission control; subsynchronous resonance; DC system transmission capacity; DC-AC system connection; EPRI proposed double-ended DC test system; HVDC system; SSDC compensation damping characteristics; UIF; backward unit interaction factor; converter station electrical damping transfer characteristic; electrical damping compensation; electrical generator capacity; forward unit interaction factor; linear model; power system stability; subsynchronous damping control; Damping; Generators; HVDC transmission; Oscillators; Rectifiers; Shafts; HVDV; SSDC; electrical damping; style; unit interaction factor;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2011 4th International Conference on
Conference_Location :
Weihai, Shandong
Print_ISBN :
978-1-4577-0364-5
Type :
conf
DOI :
10.1109/DRPT.2011.5993929