DocumentCode :
289929
Title :
Air flow measurements inside the switching center of France Telecom at Eurodisney
Author :
Arefi, S. ; Chanconie, M. ; Gomes, L. ; Goron, M.
Author_Institution :
CETIAT, Orsay, France
Volume :
1
fYear :
1993
fDate :
27-30 Sep 1993
Firstpage :
223
Abstract :
CETIAT carried out flow rate measurements inside the technical room of a telephone exchange fully equipped with electronic equipment. A false floor equipped with 54 air conditioning terminals takes charge of the air diffusion inside the room in order to remove the heat released by the equipment. CETIAT designed and realized a special flowmeter to measure the flow rate at each supplying terminal and another for the exhaust terminal. The first flowmeter is composed of a transformation piece, a CETIAT flowmeter and a fan compensating the pressure drop of the system and fixing the ambient pressure in the transformation piece. The results obtained at the floor and at the ceiling made it possible to determine the air flow distribution and diffusion inside this technical room
Keywords :
air conditioning; cooling; electronic switching systems; flow measurement; flowmeters; telephone exchanges; Eurodisney; France Telecom; air conditioning; air diffusion; air flow measurements; electronic equipment; false floor; fan; flow rate; flowmeter; heat removal; switching center; telephone exchange; Circuits; Ducts; Floors; Fluid flow measurement; Heating; Pressure measurement; Resumes; Telecommunication switching; Telephony; Temperature;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Telecommunications Energy Conference, INTELEC '93. 15th International
Conference_Location :
Paris
Print_ISBN :
0-7803-1842-0
Type :
conf
DOI :
10.1109/INTLEC.1993.388439
Filename :
388439
Link To Document :
بازگشت