DocumentCode :
2904111
Title :
Voltage transformer ferroresonance in cogeneration substation
Author :
Vilcheck, William S. ; Haddad, Michael V.
Author_Institution :
Westinghouse Electric Corp., Pittsburgh, PA, USA
fYear :
1992
fDate :
8-12 Jun 1992
Firstpage :
148
Lastpage :
158
Abstract :
An incident in which the series grading capacitance of a 230 kV circuit breaker interacted with the magnetizing reactance of a voltage transformer causing overvoltage and eventual failure of the voltage transformer is described. It is shown that this incident, including the damaging overvoltages, was successfully simulated on a digital computer. Using the same model, proposed solutions derived from transmission experience were evaluated. The most effective solution was applied to the substation circuits and measurements were taken during initial circuit breaker energization and deenergization. Measurement results are compared with analytical results
Keywords :
circuit breakers; cogeneration; digital simulation; overvoltage; potential transformers; power system analysis computing; power transformers; substations; thermal power stations; 230 kV; circuit breaker; cogeneration substation; deenergization; digital simulation; energization; failure; ferroresonance; magnetizing reactance; overvoltages; power system analysis computing; power transformers; series grading capacitance; thermal power stations; voltage transformer; Capacitance; Circuit breakers; Circuit simulation; Cogeneration; Computational modeling; Computer simulation; Ferroresonance; Substations; Voltage control; Voltage transformers;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Pulp and Paper Industry Technical Conference, 1992., Conference Record of 1992 Annual
Conference_Location :
Portland, OR
Type :
conf
DOI :
10.1109/PAPCON.1992.186293
Filename :
186293
Link To Document :
بازگشت