• DocumentCode
    2904356
  • Title

    Breakdown voltage analysis of insulating oils under different conditions

  • Author

    Kocatepe, Celal ; Arikan, Orhan ; Taslak, Eyup ; Kumru, Celal Fadil

  • Author_Institution
    Dept. of Electr. Eng., Yildiz Tech. Univ., Istanbul, Turkey
  • fYear
    2013
  • fDate
    2-4 Oct. 2013
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The dielectric performance of insulating oils used in high voltage equipment is very important for the power system continuity and reliability. In this study, breakdown voltage measurements of mineral insulating oil were carried at different temperatures and water quantity rates were researched. Additionally, the effect of water content inside the oil sample, approximately 2.5 percent, on the breakdown voltage was analyzed for particular temperatures. In the experimental study, the breakdown voltage behavior of mineral oil which is widely used in power transformers was acquired according to the ASTM D877 standard for different service conditions and the obtained results were presented.
  • Keywords
    electric breakdown; power transformer insulation; transformer oil; ASTM D877 standard; breakdown voltage analysis; breakdown voltage measurements; high voltage equipment; mineral insulating oil; power system continuity; power system reliability; power transformers; service conditions; water quantity rates; Atmospheric measurements; Oil insulation; Particle measurements; Power transformer insulation; Reliability engineering; Temperature measurement; breakdown voltage; insulating oils; mineral oil; temperature; water content;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power and Energy Conversion Systems (EPECS), 2013 3rd International Conference on
  • Conference_Location
    Istanbul
  • Print_ISBN
    978-1-4799-0687-1
  • Type

    conf

  • DOI
    10.1109/EPECS.2013.6712985
  • Filename
    6712985