Title :
Harmonic emission before and after changing to LED and CFL — Part II: Field measurements for a hotel
Author :
Rönnberg, Sarah K. ; Wahlberg, Mats ; Bollen, Math H J
Author_Institution :
Lulea Univ. of Technol., Skellefteå, Sweden
Abstract :
This paper shows the results of measurements performed with a medium-sized hotel in the North of Sweden. The harmonic emission and other parameters were measured before, during and after a replacement of all incandescent lamps with energy saving lamps, both compact fluorescent lamps (CFL´s) and light emitting diodes (LED´s). it was not possible to see any major difference in harmonic spectrum before and after the replacement. The reduction in power factor that was observed was completely due to the reduction in active power.
Keywords :
fluorescent lamps; harmonic distortion; light emitting diodes; power factor; power supply quality; CFL; LED; active power reduction; compact fluorescent lamps; energy saving lamps; field measurements; harmonic distortion; harmonic emission; harmonic spectrum; light emitting diodes; medium-sized hotel; power factor reduction; power quality; Current measurement; Distortion measurement; Harmonic analysis; Harmonic distortion; Power measurement; Power system harmonics; Reactive power; Power quality; harmonic distortion; lighting;
Conference_Titel :
Harmonics and Quality of Power (ICHQP), 2010 14th International Conference on
Conference_Location :
Bergamo
Print_ISBN :
978-1-4244-7244-4
Electronic_ISBN :
978-1-4244-7245-1
DOI :
10.1109/ICHQP.2010.5625413