DocumentCode :
2907138
Title :
The problems of centralized decrease of harmonic voltages in the HV networks with distributed nonlinear loads
Author :
Kovernikova, L.I.
Author_Institution :
Melentiev Energy Syst. Inst., SB RAS, Irkutsk, Russia
fYear :
2010
fDate :
26-29 Sept. 2010
Firstpage :
1
Lastpage :
6
Abstract :
The paper studies the problems on centralized normalization of harmonic voltages in the network with distributed nonlinear loads by the passive filters. The nonlinear loads are connected to the extended HV network at practically equal distances. Each nonlinear load is of sufficiently high power. The harmonic voltage values at the nodes of nonlinear loads connection to the supply network exceed the limits established by the standard. The paper addresses the problems of choosing the passive filters: determination of a desired value of harmonic voltages after filter installation, choice of the node for filter installation, calculation of filter parameters and evaluation of the efficiency of chosen filters for centralized normalization of harmonic voltages at the network nodes. An example of choosing the third-order filters for the real 220 kV network supplying power to traction loads is given.
Keywords :
power filters; power system harmonics; HV networks; centralized normalization; distributed nonlinear loads; filter installation; harmonic voltages; nonlinear The loads connection; passive filters; third-order filters; voltage 220 kV; Active filters; Harmonic analysis; Passive filters; Power filters; Power harmonic filters; Substations; harmonic analysis; harmonic distortion; power filters; power quality; power system harmonics;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Harmonics and Quality of Power (ICHQP), 2010 14th International Conference on
Conference_Location :
Bergamo
Print_ISBN :
978-1-4244-7244-4
Electronic_ISBN :
978-1-4244-7245-1
Type :
conf
DOI :
10.1109/ICHQP.2010.5625417
Filename :
5625417
Link To Document :
بازگشت