• DocumentCode
    2908261
  • Title

    Frequency Responses of MV voltage transformers in the range of 50 Hz to 10 kHz

  • Author

    Klatt, M. ; Meyer, J. ; Elst, M. ; Schegner, P.

  • Author_Institution
    Inst. of Electr. Power Syst. & High Voltage Eng., Tech. Univ. Dresden, Dresden, Germany
  • fYear
    2010
  • fDate
    26-29 Sept. 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Voltage quality plays an important role in modern distribution networks. One voltage quality parameter is harmonic distortion. Voltage harmonics in MV-networks are measured in most cases by using installed inductive voltage transformers (IVT). The accuracy of these transformers for frequencies above nominal frequency (50Hz or 60Hz) is usually not known. The paper presents a systematic analysis of the frequency-dependent accuracy of these IVT´s for harmonic measurements in the frequency range up to 10 kHz and it´s dependency from different factors and operating conditions. After an overview of possible factors that influence the frequency response, the used measurement equipment and methodology is described. The frequency responses of more than 85 IVT´s with rated primary voltages between 10 kV and 35 kV were measured and analysed. The significance of each influencing factor to the frequency response is discussed and finally a frequency-dependent measurement uncertainty range for 20 kV IVT´s is proposed.
  • Keywords
    distribution networks; measurement uncertainty; potential transformers; power supply quality; power system harmonics; power system measurement; MV voltage transformers; MV-networks; distribution networks; frequency 50 Hz to 10 kHz; frequency-dependent measurement uncertainty; harmonic distortion; inductive voltage transformers; voltage 10 kV; voltage 20 kV; voltage 35 kV; voltage harmonics; voltage quality parameter; Standards; frequency response; measurement errors; power quality; power system harmonics; voltage transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Harmonics and Quality of Power (ICHQP), 2010 14th International Conference on
  • Conference_Location
    Bergamo
  • Print_ISBN
    978-1-4244-7244-4
  • Electronic_ISBN
    978-1-4244-7245-1
  • Type

    conf

  • DOI
    10.1109/ICHQP.2010.5625484
  • Filename
    5625484