• DocumentCode
    2913463
  • Title

    Case study of ferroresonance in 33 kV distribution network of PEA Thailand

  • Author

    Laohacharoensombat, Kesinee ; Tuitemwong, Kamphol ; Jaruwattanadilok, Sermchai ; Wattanasakpubal, Choowong ; Kleebmek, Kritsada

  • Author_Institution
    Provincial Electr. Authority, Bangkok, Thailand
  • Volume
    C
  • fYear
    2004
  • fDate
    21-24 Nov. 2004
  • Firstpage
    417
  • Abstract
    This paper presents a study of the ferroresonance phenomena occurring on 33 kV PEA (Provincial Electricity Authority) distribution network in Satun province. The installations of 1000 kVA and 500 kVA delta-wye transformers, 300 meters underground cable and capacitor in the low side of the transformers cause the overvoltage while then are single-phase or two phase switching events. The result of overvoltage damages surge arresters that are installed at the both transformers and the connection point between partial insulated conductor (PIC) and underground cable in several times. The analysis is made by ATP-EMTP simulation compare with experimental events. The purposed solutions of this problem are determined on the simulation and field test result.
  • Keywords
    arresters; ferroresonance; overvoltage protection; power distribution protection; power engineering computing; power transformer protection; underground cables; 1000 kVA; 300 m; 33 kV; 500 kVA; ATP-EMTP simulation; PEA Thailand; Provincial Electricity Authority; capacitor; delta-wye transformers; distribution network; ferroresonance; overvoltage; partial insulated conductor; surge arresters; underground cable; Arresters; Cable insulation; Capacitors; Conductors; Ferroresonance; Power cable insulation; Power cables; Power transformer insulation; Surges; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    TENCON 2004. 2004 IEEE Region 10 Conference
  • Print_ISBN
    0-7803-8560-8
  • Type

    conf

  • DOI
    10.1109/TENCON.2004.1414796
  • Filename
    1414796