Abstract
The evaluation of the electrical energy flows is at the base of all operations connected to the electric energy commercial transactions. The assessment of "metrological quality" of the energy measurement chain, which is, in the most general case, constituted by induction CTs and VTs further on analogical or digital energy meters, is well established in ideal sinusoidal conditions. Nowadays, with the increasing diffusion of power electronics, the typical characteristics of supply networks are far from being sinusoidal. In this paper, starting from the models of the single components of the measuring chain, which take into account the variability of the accuracy with the frequency, the whole model is developed. Simulation results obtained with reference to a case-study are presented and discussed.
Keywords
analogue-digital conversion; energy measurement; power supply quality; analogical-digital energy meters; electric energy commercial transactions; electric energy revenue meter chain; energy measurement chain; metrological quality; nonsinusoidal conditions; power electronics; Current transformers; Energy measurement; Frequency measurement; Instrumentation and measurement; Measurement standards; Pollution measurement; Power electronics; Reactive power; Testing; Watthour meters; Electric energy metering; Harmonic Pollution; Power Quality; Revenue Meters;
fLanguage
English
Publisher
ieee
Conference_Titel
Instrumentation and Measurement Technology Conference Proceedings, 2007. IMTC 2007. IEEE
Conference_Location
Warsaw
ISSN
1091-5281
Print_ISBN
1-4244-0588-2
Type
conf
DOI
10.1109/IMTC.2007.379101
Filename
4258392
Link To Document