DocumentCode :
2914929
Title :
Vacuum disconnectors an application study
Author :
Schellekens, H. ; Shioiri, T. ; Homma, M. ; Picot, P. ; Sasage, K. ; Mazzucchi, D.
Author_Institution :
Schneider-Electr., Grenoble, France
fYear :
2010
fDate :
Aug. 30 2010-Sept. 3 2010
Firstpage :
117
Lastpage :
120
Abstract :
The ageing of vacuum interrupters with combined functions of disconnector and circuit-breaker or switch is studied for compact shielded solid insulated switchgear. Different prototypes are manufactured to investigate the influence of contact materials and contact designs. A test program is presented that realistically represents the ageing as described in the standards. The feasibility to create vacuum disconnecting circuit-breakers, vacuum switch-disconnectors and vacuum earthing switches that respond reliably to the requirements of the standards is demonstrated. Most of the tested designs comply with the current IEC62271-1, -100, -103 and -102 requirements for combined disconnect functions. It is shown that all combined disconnector functions can be realised with suitably designed VIs in a compact and economical way even for environmental friendly, but dielectrically very constraint, shielded solid insulated switchgear.
Keywords :
IEC standards; ageing; earthing; insulation; vacuum circuit breakers; vacuum interrupters; IEC62271-100; IEC62271-102; IEC62271-103; ageing; circuit breaker; compact shielded solid insulated switchgear; contact materials; vacuum disconnectors; vacuum earthing switches; vacuum interrupters; vacuum switch-disconnectors; Aging; Dielectric breakdown; Dielectrics; Grounding; Switches; Switchgear; Switching circuits;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum (ISDEIV), 2010 24th International Symposium on
Conference_Location :
Braunschweig
ISSN :
1093-2941
Print_ISBN :
978-1-4244-8367-9
Electronic_ISBN :
1093-2941
Type :
conf
DOI :
10.1109/DEIV.2010.5625881
Filename :
5625881
Link To Document :
بازگشت