Abstract :
60 kV vacuum interrupters (VI) for 110 kV circuit-breakers are investigated. Reduction of dielectric strength of VI in process of expiration of an electric resource is revealed at lightning pulse test. It occurs owing to reduction of dielectric strength of system “case-shield” owing to metallization of a part of an internal insulation surface of VI case with products of contact erosion. Metallization increases with reduction of switching resource. Dielectric strength of an inter-contact gap with its sufficient length does not provide dielectric strength of VI. The original shielding system providing preservation of dielectric strength of VI up to expiration of an electric resource is developed and offered.
Keywords :
electric strength; metallisation; vacuum interrupters; contact erosion; intercontact gap; internal insulation surface; lifetime degradation; lightning pulse test; metallization; vacuum interrupters dielectric strength; voltage 60 kV; Dielectric breakdown; Insulation; Interrupters; Lightning; Metallization; Switches;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum (ISDEIV), 2010 24th International Symposium on
Conference_Location :
Braunschweig
ISSN :
1093-2941
Print_ISBN :
978-1-4244-8367-9
Electronic_ISBN :
1093-2941
Type :
conf
DOI :
10.1109/DEIV.2010.5625886
Filename :
5625886
Link To Document :
بازگشت