DocumentCode
2917171
Title
Analysis of dynamic model of heating system after step change of water supply temperature
Author
Jinhai, Li ; Lide, Fang ; Suosheng, Cao ; Xiangjie, Kong
Author_Institution
Inst. of Quality & Tech. Supervision, Hebei Univ., Baoding
fYear
2008
fDate
17-20 Dec. 2008
Firstpage
1924
Lastpage
1928
Abstract
In China, the heating measurement system employed a ball valve to control the flow rate on the pipe inlet of the house. Unsurely, the valve remain turn on when the inhabitant at home and remain cut off when the inhabitant go to work, which can make a step change to water supply temperature. In this paper, the characteristic of the temperature distribution curve of radiator was analyzed in transient, the parallel moving presumption of the temperature distribution curve was proposed, according to the presumption, the functional relation between heat dissipating capacity of radiator and the time in transient was put forward, the rationality of the functional relation was proved by experiments.
Keywords
flow control; heat systems; pipes; temperature distribution; ball valve; dynamic model; flow control; functional relation; heating measurement system; pipe inlet; temperature distribution curve; water supply temperature; water supply temperature step change; Automatic control; Fluid flow measurement; Monitoring; Robotics and automation; Temperature control; Temperature distribution; Thermal conductivity; Transient analysis; Valves; Water heating; heat measuring; model; step change; transitional process; water supply temperature;
fLanguage
English
Publisher
ieee
Conference_Titel
Control, Automation, Robotics and Vision, 2008. ICARCV 2008. 10th International Conference on
Conference_Location
Hanoi
Print_ISBN
978-1-4244-2286-9
Electronic_ISBN
978-1-4244-2287-6
Type
conf
DOI
10.1109/ICARCV.2008.4795823
Filename
4795823
Link To Document