Insulation diagnosis for 220kV oil-immersed current transformer by frequency dielectric spectroscopy
Author
Peng, Hua-Dong ; Dong, Ming ; Ren, Ming ; Miao, Jin ; Zhang, Zhi
Author_Institution
State Key Lab. of Electr. Insulation & Power, Equip., Xi´´an Jiaotong Univ., Xi´´an, China
fYear
2011
fDate
5-8 June 2011
Firstpage
69
Lastpage
73
Abstract
Current transformer (CT) is used for protection of major components and to provide continuity of operation in power system. Failure of CT may lead to an energy explosion and result in phase to ground fault that will hinder the operation of a substation. Therefore insulation diagnosis is of great importance for evaluation of CT. As a non-destructive dielectric testing tool, Frequency Dielectric Spectroscopy (FDS) is widely used by power utility for assessments of the condition of electrical equipments such as transformer and cable, but seldom used on CT. Due to the similarity of transformer´s insulation, the insulation condition of oil-paper insulation CT may be evaluated by FDS. In this paper, with the frequency range from 10-2~103Hz, FDS has been investigated on insulation condition assessment for several 220kV oil-immersed CTs. Complex permittivity and dissipation factor data are obtained as a function of frequency for each CT. To verify the validity of FDS, high voltage dissipation factors from 10kV to 145kV have been measured by Schering Bridge and compared with the FDS result at power frequency. Results indicate that FDS evaluation is a reliable tool for determination of moisture content in papers and of oil conductivities.
Keywords
current transformers; nondestructive testing; permittivity; permittivity measurement; power system protection; substation protection; transformer oil; Schering Bridge; complex permittivity; dissipation factor data; electrical equipments; energy explosion; frequency dielectric spectroscopy; ground fault; insulation condition; insulation diagnosis; moisture content; nondestructive dielectric testing tool; oil conductivities; oil-immersed current transformer; oil-paper insulation; power system; power utility; substation operation; transformer insulation; voltage 10 kV to 145 kV; voltage 220 kV; Aging; Current transformers; Dielectric measurements; Dielectrics; Insulation; Moisture; Voltage measurement; aging and moisture; current transformer; dissipation factor; frequency dielectric spectroscopy;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation Conference (EIC), 2011
Conference_Location
Annapolis, MD
ISSN
pending
Print_ISBN
978-1-4577-0278-5
Electronic_ISBN
pending
Type
conf
DOI
10.1109/EIC.2011.5996118
Filename
5996118
Link To Document