• DocumentCode
    2929852
  • Title

    Interrupter pressure measurement of a 252 kV SF6 circuit breaker

  • Author

    Guan, Yonggang ; Liu, Weidong ; Wu, Junhui ; Li, Wenyi

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
  • fYear
    2011
  • fDate
    23-27 Oct. 2011
  • Firstpage
    160
  • Lastpage
    163
  • Abstract
    The transient pressure process, which determined the gas blasting in the interrupter of SF6 circuit breaker, have attracted the attention of designer and developer for long time. In this investigation, a on-load SF6 interrupter pressure measurement method was established with piezoresistive pressure transducer and insulating-tube. The pressures in the puffer cylinder, at the upstream, throat and downstream of nozzle have been measured. The difference of gas blowing characteristics between N2 and SF6 has been pointed out. The insulating-tube can effectively protect the pressure transducer from the high voltage and high temperature during on-load interrupting. It was found that the arc process can cause high frequency oscillations to superimpose upon the pressure waveforms during on-load interrupting.
  • Keywords
    SF6 insulation; arcs (electric); gas blast circuit breakers; interrupters; pressure measurement; pressure transducers; SF6; arc process; circuit breaker; frequency oscillations; gas blasting; gas blowing; insulating tube; interrupter pressure measurement; nozzle; piezoresistive pressure transducer; puffer cylinder; throat; transient pressure; voltage 252 kV; Circuit breakers; Current measurement; Interrupters; Pressure measurement; Sulfur hexafluoride; Temperature measurement; Transducers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Equipment - Switching Technology (ICEPE-ST), 2011 1st International Conference on
  • Conference_Location
    Xi´an
  • Print_ISBN
    978-1-4577-1273-9
  • Type

    conf

  • DOI
    10.1109/ICEPE-ST.2011.6122959
  • Filename
    6122959