Effection on Short-Circuit Current Limit of 500kV Autotransformer Neutral Grounding via Small Reactance
Author :
Liang Jifeng ; Liu Wenying ; Li Yang ; Jin Na ; Li Xiaorong
Author_Institution :
Sch. of Electr. & Electron. Eng., North China Electr. Power Univ., Beijing, China
fYear :
2011
fDate :
25-28 March 2011
Firstpage :
1
Lastpage :
4
Abstract :
In this paper, with strengthening of the power grid structure recently, part of Regional Power Grid 220kV Bus single-Phase short-circuit current exceeding the three-phase short-current, First analyzed the structure of the North China Power Grid Status, power grid characteristics and the structural features of main transformer in 500kV substation, and According that making out the reasons that 220kV single-phase short-circuit current increased dramatically. According to the North China Power Grid 2009 winter big load data, selected the Anding Station, Shunyi Station, Binhai Station and Baobei Station in the North China Power Grid, used the Power System Analysis Software Package (PSASP), made main transformer neutral grounding via low resistance electrical short-circuit current calculation. According to short-circuit current calculation, analyzed the limiting effects of 500kV autotransformer neutral grounding by small reactance on 220kV single-phase short circuit current, grid structure on the low reactance limiting effects, and gived a project guidance about small reactor´s selection.
Keywords :
autotransformers; earthing; fault current limiters; power grids; power system analysis computing; short-circuit currents; substations; Anding Station; Baobei Station; Binhai Station; North China Power Grid 2009 winter big load data; North China Power Grid Status; Regional Power Grid bus single-phase short-circuit current; Shunyi Station; autotransformer neutral grounding; grid structure; low reactance limiting effects; low resistance electrical short-circuit current calculation; power grid characteristics; power system analysis software package; short-circuit current limit; small reactor selection; substation; voltage 220 kV; voltage 500 kV; Grounding; Impedance; Limiting; Power grids; Power transformer insulation; Substations;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
Conference_Location :
Wuhan
ISSN :
2157-4839
Print_ISBN :
978-1-4244-6253-7
Type :
conf
DOI :
10.1109/APPEEC.2011.5748653
Filename :
5748653
Link To Document :
بازگشت