• DocumentCode
    2933685
  • Title

    Research on DC Transient Overvoltage and Insulation Coordination of ±800kV Converter Station

  • Author

    Han Yongxia ; Chen Huixiang ; Lu Yuxin ; Li Licheng

  • Author_Institution
    Guangdong Electr. Power Design Inst., Guangzhou, China
  • fYear
    2011
  • fDate
    25-28 March 2011
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    It is very important for the ±800kV UHVDC transmission project to study the overvoltage protection and insulation coordination of the converter stations because of its importance in the power grid. The paper studies the DC transient overvoltage of the converter station in the Nuozhadu-Guangdong ±800kV UHVDC transmission project by using the PSCAD simulation program. The simulation results show that the overvoltages on the equipments are influenced by the modeling methods and control strategy of the UHVDC system, and the overvoltages on several arresters are over their protective levels. At last, proper measures are put forward and analyzed for improving the insulation coordination scheme of the ±800kV converter station.
  • Keywords
    HVDC power convertors; HVDC power transmission; arresters; insulation co-ordination; overvoltage protection; power grids; DC transient overvolatge; PSCAD simulation program; UHVDC transmission project; arresters; converter station; insulation coordination; overvoltage protection; power grid; voltage -800 kV; voltage 800 kV; Arresters; Converters; Insulation; Lightning; Power transmission lines; Simulation; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
  • Conference_Location
    Wuhan
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4244-6253-7
  • Type

    conf

  • DOI
    10.1109/APPEEC.2011.5748736
  • Filename
    5748736