• DocumentCode
    2934465
  • Title

    Calculation of Power Frequency Electric Field in HV Substation Using BEM

  • Author

    Tang Ling ; Wang Xiaoyu ; Qiao Liang ; Sun Lu ; Yang Fan

  • Author_Institution
    Dept. of Electron. Eng., Sichuan Univ. of Sci. & Eng., Zigong, China
  • fYear
    2011
  • fDate
    25-28 March 2011
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The power frequency electric field in the HV substation has aroused more and more attention. In the paper, the power frequency electric field in 500kV substation is calculated using the boundary element method considering the influence of the switching equipment. According to the structural characteristics of the switching equipments, the indirect boundary integral equation of the suspension electrode was formulated. The modeling method and procedure for the power frequency electric field calculation in the substation are presented. Finally, a typical 500kV substation is taken as an example for the calculation on the power-frequency electric filed,, the IES coulomb is used, and results indicate that the power frequency electric field depends mainly on the height of the bus bar. To decrease the influence on the environment caused by the HV transmission lines and switching equipment, the height of the bus bar should be increased.
  • Keywords
    boundary-elements methods; busbars; electric fields; integral equations; transformer substations; HV substation; HV transmission lines; IES coulomb; boundary-elements methods; bus bar; indirect boundary integral equation; power frequency electric field; suspension electrode; switching equipment; transformer substations; voltage 500 kV; Electric fields; Equations; Mathematical model; Power transmission lines; Substations; Switches; Transmission line measurements;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
  • Conference_Location
    Wuhan
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4244-6253-7
  • Type

    conf

  • DOI
    10.1109/APPEEC.2011.5748775
  • Filename
    5748775