DocumentCode
2936642
Title
Study on Contamination Deposition Characteristics of Transmission Line Insulators
Author
Gu, Chunhui ; Li, Jiangtao ; Li, Meng ; Zhang, Leizhou ; Zhang, Wei ; Zhang, Qiaogen ; Qian, Zhiyin ; Xiao, Rong ; Fu, Chenzhao
Author_Institution
State Key Lab. of Electr. Insulation & Power Equip., Xi´´an Jiaotong Univ., Xi´´an, China
fYear
2011
fDate
25-28 March 2011
Firstpage
1
Lastpage
4
Abstract
Pollution flashover accident of insulators may threaten the safety and stability of power system; however, there lacks an effective way to evaluate this potential risk, because the rule of contaminant deposition is still not fairly known. Artificial contamination tests are carried out to study the contamination deposition characteristics which may give help to evaluate the flashover probability. The results show that the amount of the contaminants on each section of the insulator has clear connections to the wind speed and direction. The amount and the distribution of the contaminants on the insulator surface are highly correlated to the flashover voltage. With the decrease of wind velocity, Equivalent salt deposit density values of transmission line insulators show the increasing tendency.
Keywords
flashover; power cable insulation; power transmission lines; artificial contamination tests; contamination deposition; insulator surface; pollution flashover accident; tansmission line insulators; wind direction; wind speed; Flashover; Insulators; Pollution measurement; Surface contamination; Surface treatment; Wind speed;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
Conference_Location
Wuhan
ISSN
2157-4839
Print_ISBN
978-1-4244-6253-7
Type
conf
DOI
10.1109/APPEEC.2011.5748879
Filename
5748879
Link To Document