DocumentCode
294118
Title
Inverting DC traction substation with active power filtering incorporated
Author
Randewijk, Peter-Jan ; Enslin, Johan HR
Author_Institution
Dept. of Electr. & Electron. Eng., Stellenbosch Univ., South Africa
Volume
1
fYear
1995
fDate
18-22 Jun 1995
Firstpage
360
Abstract
A new type of reversible traction substation is proposed and a small test of concept model was built and investigated. The test of concept consists of a 10 kVA three-phase IGBT inverter placed in anti-parallel with a 75 kVA three-phase diode rectifier. The inverter is not only capable of pumping energy back into the AC power supply during excessive regeneration, but also acts as dynamic power filtering (DPF) during normal traction load conditions. The total control algorithm for the inverter/DPF is implemented on a TMS320C31 digital signal processor (DSP)
Keywords
AC-DC power convertors; PWM invertors; PWM power convertors; active filters; load (electric); power filters; power supplies to apparatus; power system harmonics; railways; rectifiers; substations; traction; 10 kVA; 75 kVA; AC power supply; DC traction substation; active power filtering; anti-parallel connection; control algorithm; excessive regeneration; reversible power flow; three-phase IGBT inverter; three-phase diode rectifier; traction load; Active filters; Diodes; Filtering; Insulated gate bipolar transistors; Inverters; Power filters; Rectifiers; Substations; Testing; Traction power supplies;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics Specialists Conference, 1995. PESC '95 Record., 26th Annual IEEE
Conference_Location
Atlanta, GA
Print_ISBN
0-7803-2730-6
Type
conf
DOI
10.1109/PESC.1995.474836
Filename
474836
Link To Document