DocumentCode :
2941729
Title :
Exergy Evaluation of Direct Sewage Source Heat Pump System
Author :
Qian, Jianfeng
Author_Institution :
Sch. of Energy & Civil Eng., Harbin Univ. of Commerce, Harbin, China
fYear :
2011
fDate :
25-28 March 2011
Firstpage :
1
Lastpage :
4
Abstract :
Sewage source heat pump system plays a significant role in energy-saving and environmental protection which can be divided into direct and indirect system. For the shortcoming of research on the direct one, some anti-scaling technology and the heat exchangers to remove the soft dirt are introduced. Based on the exergy method, an analysis is given of energy efficiency in the direct sewage source heat pump. The conclusions are educed by an example that exergy efficiency is higher 4% or 6.5% at the heating or cooling condition in the direct system than the indirect one.
Keywords :
environmental factors; exergy; heat exchangers; heat pumps; sewage treatment; anti-scaling technology; cooling condition; direct sewage source heat pump system; energy-saving; environmental protection; exergy evaluation; heat exchangers; heating condition; Cooling; Heat pumps; Heat transfer; Heating; Sun; Thermodynamics; Waste heat;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
Conference_Location :
Wuhan
ISSN :
2157-4839
Print_ISBN :
978-1-4244-6253-7
Type :
conf
DOI :
10.1109/APPEEC.2011.5749135
Filename :
5749135
Link To Document :
بازگشت