DocumentCode
2952054
Title
Simulation of PD location using Power Transformer Model Winding
Author
Gurumurthy, G.R. ; Kini, Sushma S.
Author_Institution
Dept. of Electr.&Electron. Eng., BNM Inst. of Technol., Bangalore
fYear
2008
fDate
8-10 Dec. 2008
Firstpage
1
Lastpage
5
Abstract
Partial discharge location in power transformers has been investigated by carrying out simulation on a representative model winding. The transformer model winding for analysing simulated partial discharges is represented to consist of sections having series inductances, mutual inductances between sections, series capacitance across section and shunt capacitances between terminals of section to ground. The investigation have shown that PD location accuracies using travelling wave method are good for windings having `alpha´ (alpha) values equal to or grater than 12. For low ´alpha´ value windings (in range 4 to 8), use of suitable filters along with pulse integrators has shown improvements in PD location accuracies for length of winding upto 25% from end terminals of winding.
Keywords
partial discharges; power transformers; partial discharge location; power transformers; pulse integrators; simulated partial discharges analysis; transformer model winding; travelling wave method; Capacitance; Dielectrics and electrical insulation; Fault location; Oil insulation; Partial discharges; Power engineering and energy; Power transformer insulation; Power transformers; Pulse transformers; Windings; Location; PD; Transformer winding; Travel time; ¿Value;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial and Information Systems, 2008. ICIIS 2008. IEEE Region 10 and the Third international Conference on
Conference_Location
Kharagpur
Print_ISBN
978-1-4244-2806-9
Electronic_ISBN
978-1-4244-2806-9
Type
conf
DOI
10.1109/ICIINFS.2008.4798388
Filename
4798388