• DocumentCode
    2952054
  • Title

    Simulation of PD location using Power Transformer Model Winding

  • Author

    Gurumurthy, G.R. ; Kini, Sushma S.

  • Author_Institution
    Dept. of Electr.&Electron. Eng., BNM Inst. of Technol., Bangalore
  • fYear
    2008
  • fDate
    8-10 Dec. 2008
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Partial discharge location in power transformers has been investigated by carrying out simulation on a representative model winding. The transformer model winding for analysing simulated partial discharges is represented to consist of sections having series inductances, mutual inductances between sections, series capacitance across section and shunt capacitances between terminals of section to ground. The investigation have shown that PD location accuracies using travelling wave method are good for windings having `alpha´ (alpha) values equal to or grater than 12. For low ´alpha´ value windings (in range 4 to 8), use of suitable filters along with pulse integrators has shown improvements in PD location accuracies for length of winding upto 25% from end terminals of winding.
  • Keywords
    partial discharges; power transformers; partial discharge location; power transformers; pulse integrators; simulated partial discharges analysis; transformer model winding; travelling wave method; Capacitance; Dielectrics and electrical insulation; Fault location; Oil insulation; Partial discharges; Power engineering and energy; Power transformer insulation; Power transformers; Pulse transformers; Windings; Location; PD; Transformer winding; Travel time; ¿Value;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial and Information Systems, 2008. ICIIS 2008. IEEE Region 10 and the Third international Conference on
  • Conference_Location
    Kharagpur
  • Print_ISBN
    978-1-4244-2806-9
  • Electronic_ISBN
    978-1-4244-2806-9
  • Type

    conf

  • DOI
    10.1109/ICIINFS.2008.4798388
  • Filename
    4798388