    Analysis of dissolved gases extraction processes in transformer oil for chromatography

  • Author

    Darian, L.A. ; Korobeynikov, S.M.

  • Author_Institution
    Novosibirsk State Tech. Univ., Novosibirsk
  • fYear
    2007
  • fDate
    3-6 Oct. 2007
  • Firstpage
    261
  • Lastpage
    264
  • Abstract
    The main diffusion processes that are in devices for testing of transformer oil for gas chromatography are considered. The estimation of time for safety storage of most movable gas in transformer oil - hydrogen in several types of syringes is shown. It is obtained that the most suitable device is ldquoElchromldquo, where used both glass frame of syringe and glass plunger. Besides it has PTFE sealing gasket that lead to the safety of the gas in probing during more than one month. The equilibration time for gas in oil and gas in gas phase is estimated for some devices of gas extraction.
  • Keywords
    chromatography; diffusion; hydrogen; safety; transformer oil; Elchrom; PTFE sealing gasket; diffusion processes; dissolved gases extraction processes; gas chromatography; glass plunger; hydrogen; safety storage; syringes; time estimation; transformer oil; Diffusion processes; Dissolved gas analysis; Gas chromatography; Gases; Gaskets; Glass; Hydrogen storage; Oil insulation; Safety; Testing;