DocumentCode :
2956641
Title :
Improved quality of supply in MV distribution networks using directional blocking scheme
Author :
Tobias, J.C. ; Sautriau, F. ; Hull, D.J. ; Fabray, S.
Author_Institution :
Schneider Ltd., Merlin Gerin, UK
Volume :
4
fYear :
1997
fDate :
1997
Abstract :
Electricity distribution companies serving modern metropolitan areas and automated industries will come under increasing pressure to reduce the impact of short interruptions and voltage dips. This can only be achieved by using sectionalising circuit breakers and unit protected feeders. The present paper describes a trial scheme in Hong Kong which showed that directional blocking unit protection can deliver improved quality of supply. In the case of the Hon Kong Electric Company, it was possible to use available VF channels for signalling. However, the scheme could have universal application if the blocking signals are transmitted on the MV power line
Keywords :
distribution networks; 11 kV; Hong Kong; MV distribution network protection; VF channels; directional blocking scheme; electricity distribution companies; metropolitan areas; power interruptions; power quality improvement; power system telecontrol; sectionalising circuit breakers; signalling; unit protected feeders; voltage dips;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution. Part 1: Contributions. CIRED. 14th International Conference and Exhibition on (IEE Conf. Publ. No. 438)
Conference_Location :
Birmingham
ISSN :
0537-9989
Print_ISBN :
0-85296-674-1
Type :
conf
DOI :
10.1049/cp:19970576
Filename :
671680
Link To Document :
بازگشت