Overvoltages produced in line due to transferring from and to diesel engine
Author
Jaureguialzo, Enrique ; Sarrajj, Ezzedin
Author_Institution
Chloride Power Protection, Barcelona
fYear
2007
fDate
Sept. 30 2007-Oct. 4 2007
Firstpage
223
Lastpage
227
Abstract
When a neutral pole is switched during a commutation between two sources (like a line to GE commutation and vice versa after a line failure), and a third source is installed downstream (like a UPS), dangerous neutral to ground and line to ground overvoltages can appear. These overvoltages can produce problems in the installation process such as differential tripping and the blocking or destruction of equipment etc. The solutions depend on the neutral scheme; they can affect the differential protections upstream of the commutation or infringe the electrical normative rules. That´s why it is very important to take special care during the installation project in order to prevent any undesired effects of the commutation. The purpose of this paper is therefore to describe this phenomenon and its consequences to the installation, giving the solutions and their associated problems, i.e. normative violations or differential protections.
Keywords
diesel engines; overvoltage protection; diesel engine; differential tripping; ground overvoltages; installation process; neutral pole; Cities and towns; Communication industry; Diesel engines; Emergency power supplies; Network neutrality; Power system protection; Surge protection; Switches; Uninterruptible power systems; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 2007. INTELEC 2007. 29th International
Conference_Location
Rome
Print_ISBN
978-1-4244-1627-1
Electronic_ISBN
978-1-4244-1628-8
Type
conf
DOI
10.1109/INTLEC.2007.4448771
Filename
4448771
Link To Document