DocumentCode :
2965511
Title :
A method for calculating equivalent circuit constants of a synchronous generator with damper using a DC decay test with open and shorted field windings
Author :
Kano, Takashi ; Ara, Takahiro ; Matsumura, Toshiro
Author_Institution :
Nagoya Univ., Nagoya
fYear :
2008
fDate :
6-9 Sept. 2008
Firstpage :
1
Lastpage :
6
Abstract :
The authors describe a method for calculating equivalent circuit constants of synchronous generators using open and shorted operational impedances obtained by the DC decay tests. In the proposed method, it is possible to find all constants only by a stationary test, including the armature leakage reactance. This method makes it possible to improve transient analysis accuracy on not only the armature side current but also the field side. Especially the issue of field current error can be resolved. The validity of the proposed method is demonstrated by a sudden three-phase short-circuit test on a salient laminated pole machine of 10 kVA-200 V-31.9 A-4 P-50 Hz.
Keywords :
electrical faults; equivalent circuits; machine testing; machine windings; synchronous generators; transient analysis; DC decay test; apparent power 10 kVA; armature leakage reactance; current 31.9 A; equivalent circuit constants; field current error; frequency 50 Hz; open field windings; shorted field windings; stationary test; synchronous generators; transient analysis; voltage 200 V; Circuit simulation; Circuit testing; Current measurement; Damping; Electrical resistance measurement; Equivalent circuits; Impedance; Power system transients; Shock absorbers; Synchronous generators;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Machines, 2008. ICEM 2008. 18th International Conference on
Conference_Location :
Vilamoura
Print_ISBN :
978-1-4244-1735-3
Electronic_ISBN :
978-1-4244-1736-0
Type :
conf
DOI :
10.1109/ICELMACH.2008.4799844
Filename :
4799844
Link To Document :
بازگشت