  • Title

    Investigation on influence of current interruption on V-t characteristics of vacuum interrupters

  • Author

    Furukawa, Toshihiro ; Ueda, Makoto ; Hidaka, K. ; Ikeda, Hinata ; Kumada, A. ; Sato, Seiki ; Nishimura, S. ; Shimizu, Hiroshi ; Shioiri, Tetsu ; Homma, Mitsutaka

  • Author_Institution
    Univ. of Tokyo, Tokyo, Japan
  • fYear
    2012
  • fDate
    2-7 Sept. 2012
  • Firstpage
    14
  • Lastpage
    17
  • Abstract
    To identify the influence of current interruption on the insulation strength of vacuum interrupters (VIs), the V-t characteristics of VIs were measured from nano seconds to several micro seconds range before and after current interruption. The breakdown voltage increased after the current interruption for VIs of Cu-Cr contacts. The field emission current of contacts were also measured before and after the current interruption, and the change of the field enhancement factor β was investigated by Fowler-Nordheim (F-N) analysis. The analysis indicated that the surface condition was improved by the current interruption, which can explain the improvement of breakdown voltage. It also turned out that the impulse voltage application during the V-t characteristics measurement had a considerable influence on the surface condition.
  • Keywords
    electric breakdown; vacuum circuit breakers; vacuum interrupters; F-N analysis; Fowler-Nordheim analysis; V-t characteristics; current interruption; field emission current; vacuum circuit breakers; vacuum interrupters; Anodes; Cathodes; Current measurement; Insulation; Interrupters; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Discharges and Electrical Insulation in Vacuum (ISDEIV), 2012 25th International Symposium on
  • Conference_Location
    Tomsk
  • ISSN
    1093-2941
  • Print_ISBN
    978-1-4673-1263-9
  • Electronic_ISBN
    1093-2941
  • Type

    conf

  • DOI
    10.1109/DEIV.2012.6412438
  • Filename
    6412438