• DocumentCode
    2969570
  • Title

    Interrupting capability of the AMF electrodes in the external transverse field

  • Author

    Poluyanova, Irina N. ; Bugayov, Vladimir A.

  • Author_Institution
    Tavrida Electr. Design Bur., Sevastopol, Ukraine
  • fYear
    2012
  • fDate
    2-7 Sept. 2012
  • Firstpage
    244
  • Lastpage
    247
  • Abstract
    The paper demonstrates the results of experimental study of AMF CuCr electrodes interrupting capability in the presence and absence of an external transverse magnetic field. It is shown that the transverse magnetic field can significantly decrease the interrupting capability in case the long (7-9ms) arcs: under the experimental conditions the reduction of about 20% was observed. The decrease of interrupting capability is explained by the higher energy impact into the electrodes due to the rise of the arc voltage under TMF. Successfully interrupted energy density does not depend on the transverse magnetic field level. In the case of short (2.5-3.5ms) arcs the influence of transverse field on the interrupting capability is not revealed.
  • Keywords
    copper compounds; electrical contacts; electrodes; magnetic fields; vacuum arcs; vacuum circuit breakers; vacuum interrupters; AMF electrodes; CuCr; arcs voltage; external transverse magnetic field; interrupted energy density; time 2.5 ms to 3.5 ms; time 7 ms to 9 ms; vacuum circuit breakers; Anodes; Discharges (electric); Insulation; Interrupters; Magnetic fields; Vacuum arcs;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Discharges and Electrical Insulation in Vacuum (ISDEIV), 2012 25th International Symposium on
  • Conference_Location
    Tomsk
  • ISSN
    1093-2941
  • Print_ISBN
    978-1-4673-1263-9
  • Electronic_ISBN
    1093-2941
  • Type

    conf

  • DOI
    10.1109/DEIV.2012.6412498
  • Filename
    6412498