• DocumentCode
    2971235
  • Title

    VCB contact system electrical endurance on-line condition monitoring technology and its application

  • Author

    He Jia-min ; Fan Xing-ming ; Zhang Xin ; Huang Zhi-chao ; Zou Qi-tao ; Liang Cong ; Shi Wei-jian

  • Author_Institution
    Dept. of Electr. Eng. & Autom., Guilin Univ. of Electron. & Technol., Guilin, China
  • fYear
    2012
  • fDate
    2-7 Sept. 2012
  • Firstpage
    513
  • Lastpage
    516
  • Abstract
    In order to reduce the number of accidents and prevent possible troubles due to the failures of VCBs, one valid way is to monitor their performance and condition on-line. Based on the understanding and development of condition based maintenance (CBM) of high-voltage circuit breakers, the authors give some general introduction to electrical endurance on-line condition monitor for VCBs, in which the stress put on the non-intrusive method and device for determination of the arcing duration. The principle and configuration for arcing duration detect are emphatically expounded in our research, in which the electromagnetic induction theory is adopted for the arcing initialization and duration detect. The simulation and experimental results of the arcing detect device are provided in detail. The accuracy and stability of the arcing detect device have been demonstrated and it can distinguish co-existing arc signals in three-phase of circuit breakers. In the end, an algorithm for the electrical endurance of vacuum circuit breakers on-line condition monitoring system is proposed, which based on TMS320F2812 one type of DSP281X series produced by Texas Instruments semiconductor. The universally accepted approach of accumulative breaking current of high voltage circuit breaker contact to diagnose electrical endurance is used in the High-voltage Circuit Breakers Electrical Endurance On-line Monitor system.
  • Keywords
    arcs (electric); condition monitoring; electrical contacts; electrical maintenance; vacuum circuit breakers; DSP281X series; TMS320F2812 series; arcing detect device; breaking current; condition based maintenance; high voltage circuit breaker contact; high voltage circuit breakers electrical endurance; on-line condition monitoring system; on-line condition monitoring technology; vacuum circuit breaker contact system; Circuit breakers; Coils; Contacts; Detectors; Educational institutions; Indexes; Monitoring;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Discharges and Electrical Insulation in Vacuum (ISDEIV), 2012 25th International Symposium on
  • Conference_Location
    Tomsk
  • ISSN
    1093-2941
  • Print_ISBN
    978-1-4673-1263-9
  • Electronic_ISBN
    1093-2941
  • Type

    conf

  • DOI
    10.1109/DEIV.2012.6412568
  • Filename
    6412568