Abstract :
The paper describes a time-stepped coupled-circuit model for a doubly-fed induction generator. The model, which is based on the summation of the harmonic winding inductances, is capable of representing both open- and short-circuit stator and rotor winding faults. The main purpose of this paper is to present evidence of the validity of this versatile and powerful technique and the advantages it offers when used for modeling and analysis of doubly-fed induction generator operation in unbalanced conditions.
Keywords :
asynchronous generators; rotors; stators; windings; DFIG; doubly-fed induction generator; harmonic winding inductances; open-circuit stator; rotor winding faults; short-circuit stator; time-stepped coupled-circuit model; Character generation; Circuit faults; Coupling circuits; Frequency; Induction generators; Power generation; Rotors; Stator windings; Wind energy generation; Wind power generation;