• DocumentCode
    2986744
  • Title

    A unified approach to robust meter placement against loss of measurements and branch outages

  • Author

    Magnago, F.H. ; Abur, Ali

  • Author_Institution
    Dept. of Electr. Eng., Texas A&M Univ., College Station, TX, USA
  • fYear
    1999
  • fDate
    36342
  • Firstpage
    3
  • Lastpage
    8
  • Abstract
    This paper presents a systematic procedure by which measurement systems can be optimally upgraded. The proposed procedure yields a measurement configuration that can withstand any single branch outage or loss of single measurement, without losing network observability. It is a numerical method based on the measurement Jacobian and sparse triangular factorization, making its implementation easy in existing state estimators. It can be used offline in planning and meter placement studies or it can be implemented as part of the online observability analysis function. Details of the procedure are presented using numerical examples
  • Keywords
    integer programming; observability; power system analysis computing; power system measurement; power system planning; power system state estimation; branch outages; computer simulation; loss of measurements; measurement Jacobian; measurement configuration; network observability; offline planning studies; online observability analysis function; power system measurement planning; robust meter placement; sparse triangular factorization; state estimators; Costs; Jacobian matrices; Loss measurement; Monitoring; Observability; Power system measurements; Power system planning; Power system reliability; Robustness; State estimation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Industry Computer Applications, 1999. PICA '99. Proceedings of the 21st 1999 IEEE International Conference
  • Conference_Location
    Santa Clara, CA
  • Print_ISBN
    0-7803-5478-8
  • Type

    conf

  • DOI
    10.1109/PICA.1999.779378
  • Filename
    779378