  • Abstract
    This paper presents a preliminary investigation on the evaluation of ageing in 11 kV XLPE cable using return voltage measurement (RVM) method. Accelerated ageing using AC voltage was performed on new XLPE cable samples. Within the period of ageing, the state of insulation was investigated and assessed. The result of the diagnosis using the RVM showed a good correlation between aging time and the return voltage initial slopes (dU,/dt) of the aged XLPE cables, indicating the samples have undergone thermal ageing. The RVM technique, which was initially proposed for diagnosis of oil-paper insulation systems, was found to be able to detect ageing in XLPE cables, and thus insulation diagnosis using this technique could be extended to extruded-polymeric insulation systems.
  • Keywords
    XLPE insulation; insulating oils; power cable insulation; voltage measurement; XLPE cable diagnosis; extruded-polymeric insulation systems; insulation diagnosis; oil-paper insulation systems; return voltage initial slopes; return voltage measurement; Aging; Cable insulation; Dielectric measurements; Dielectrics and electrical insulation; Oil insulation; Power cable insulation; Power cables; Power system reliability; Underground power cables; Voltage measurement; RVM; XLPE cable; ageing; diagnosis; recovery voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Research and Development, 2007. SCOReD 2007. 5th Student Conference on
  • Conference_Location
    Selangor, Malaysia
  • Print_ISBN
    978-1-4244-1469-7
  • Electronic_ISBN
    978-1-4244-1470-3
  • Type

    conf

  • DOI
    10.1109/SCORED.2007.4451441
  • Filename
    4451441