Title :
In-service diagnostic of polymeric insulators exposed to severe contamination
Author :
Hernández-Corona, Ramiro ; Montoya-Tena, Gerardo
Author_Institution :
Inst. de Investigaciones Electr. (IIE), Morelos
Abstract :
In Mexico since 1995, polymeric insulators have been used in transmission lines exposed to severe contamination. Insulators from different manufacturers have been installed; however, some of them have failed during their early operation years. Consequently, since 2003, in-service diagnostic has been periodically carried out to identify high risk insulators, by using the visual corona and electric field measurement techniques. In this paper, the most important results obtained from different inspections performed in-service to polymeric insulators on Mexican transmission lines are presented. These results show that the visual corona and electric field measurement techniques can be used to identify high risk polymeric insulators prior to failure.
Keywords :
corona; electric field measurement; inspection; insulator contamination; polymer insulators; power transmission lines; Mexican transmission lines; contamination; electric field measurement techniques; in-service diagnostis; inspections; polymeric insulators; visual corona techniques; Contamination; Corona; Dielectrics and electrical insulation; Inspection; Leakage current; Plastic insulation; Poles and towers; Pollution measurement; Polymers; Transmission lines;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2007. CEIDP 2007. Annual Report - Conference on
Conference_Location :
Vancouver, BC
Print_ISBN :
978-1-4244-1482-6
Electronic_ISBN :
978-1-4244-1482-6
DOI :
10.1109/CEIDP.2007.4451580