DocumentCode
3010580
Title
Single-phase Active Power Filter based on Rotating Reference Frame Method
Author
Kim, Y.J. ; Kim, J.S. ; Kim, Y.S.
Author_Institution
Dept. of Comput. Aided Control, Yuhan Coll., Bucheon
Volume
2
fYear
2005
fDate
29-29 Sept. 2005
Firstpage
1428
Lastpage
1431
Abstract
This paper presents a new control method of the single-phase active power filter (APF) for the compensation of harmonic current components in nonlinear loads. In order to use a new transformation theory, the two-phase system by constructing a imaginary second-phase is formed. In the conventional method, an imaginary-phase lagged to the load current T/4(here T is the fundamental cycle) is made. But in this proposed method, the new signal as the second phase is the delayed through the filter. As this control method is applied to the system of single-phase, an instantaneous calculation was developed rather by using the rotating reference frames synchronized with source-frequency than by applying instantaneous reactive power theory that uses the conventional fixed reference frames. The control scheme of single-phase APF is analyzed with the experimental results in a laboratory prototype to verify the validities of the proposed control methods
Keywords
active filters; compensation; power harmonic filters; reactive power; harmonic current component; instantaneous reactive power theory; nonlinear loads; rotating reference frame method; single-phase active power filter; transformation theory; two-phase system; Active filters; Angular velocity; Control systems; Delay; Educational institutions; Laboratories; Power engineering computing; Power harmonic filters; Power system harmonics; Reactive power control;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Machines and Systems, 2005. ICEMS 2005. Proceedings of the Eighth International Conference on
Conference_Location
Nanjing
Print_ISBN
7-5062-7407-8
Type
conf
DOI
10.1109/ICEMS.2005.202784
Filename
1575017
Link To Document