• DocumentCode
    3011130
  • Title

    The criteria of dissolved gas analysis in natural ester fluid

  • Author

    Kweon Dongjin ; Koo Kyosun

  • Author_Institution
    Power Syst. Lab., KEPCO Res. Inst., Daejeon, South Korea
  • fYear
    2012
  • fDate
    23-27 Sept. 2012
  • Firstpage
    901
  • Lastpage
    904
  • Abstract
    In this paper, dissolved gasses of natural ester fluid were analyzed to suggest DGA criteria for transformer filled with natural ester fluid. Samples of mineral oil and natural ester fluid made to correspond to the ratios of the iron core, winding, insulating materials and insulating oil in a transformer were deteriorated for 1,600 hours in a 150°C thermostat and samples were collected every two hundred hours to analyze changes in the contents of dissolved gases. As the results, H2 and C2H2 gases were hardly detected and C2H6 gas detected from natural ester fluid was two times larger in quantity than mineral oil. CH4 gas detected from natural ester fluid was 1/4 in quantity of the gas detected from mineral oil. Amount of other dissolved gasses were similar to each other. Based on these results, DGA criteria for transformers applied with natural ester fluid were presented.
  • Keywords
    carbon compounds; chemical analysis; transformer oil; C2H2; C2H6; CH4; dissolved gas analysis; insulating materials; insulating oil; iron core; mineral oil; natural ester fluid; temperature 150 C; time 1600 hour; transformer; winding; Gases; Minerals; Oil insulation; Power transformer insulation; Criteria; DGA; Natural Ester; Transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis (CMD), 2012 International Conference on
  • Conference_Location
    Bali
  • Print_ISBN
    978-1-4673-1019-2
  • Type

    conf

  • DOI
    10.1109/CMD.2012.6416297
  • Filename
    6416297